Water Testing

 

All New York State public schools and Boards of Cooperative Educational Services (BOCES) are required to test all potable water outlets. 

 

  • Results of the first draw testing:

    FLOOR – Third
    FUNCTION/SPACE – Classroom 

    ROOM – 317 

    FIXTURE TYPE – Both sink faucets

    SAMPLE RESULTS – 7.6 and 6.1

    FLOOR – First
    FUNCTION/SPACE – Classroom

    ROOM – 139

    FIXTURE TYPE – Sink Faucet

    SAMPLE RESULTS – 10.1

    FLOOR – First
    FUNCTION/SPACE – Cafeteria

    ROOM – Kitchen

    FIXTURE TYPE – Left Cooking Kettle

    SAMPLE RESULTS – 5.2

     

    What is being done in response to the results?
    To remediate the areas that tested above the action level (5 ppb), the district is working with outside companies for quotes to install inline filters and/or remove old piping and install new lead-free piping. Once this work is completed, the outlets will be retested. Until retesting can occur, the outlets that were tested with lead levels above the action level (5 ppb) were removed from service unless an outlet is a sink faucet needed for handwashing. In that case, a sign was posted at the outlet indicating that the sink was not to be used for drinking. Outlets that tested below the action level remain in service with no restrictions.